Area of Earthing conductor (mm2) When It is Same Material as Phase Conductor
Area of Earthing conductor (mm2) When It is Not Same Material as Phase Conductor
S < 16 mm2
S
SX(k1/k2)
16 mm2<S< 35 mm2
16 mm2
16X(k1/k2)
S > 35 mm2
S/2
SX(k1/2k2)
*K1 is value of Phase conductor,k2 is value of earthing conductor
*Value of K for GI=80, Alu=126,Cu=205 for 1 Sec
Any suggestions or thoughts on how to improve The Book Of Engineering would be much appreciated. Please don't hesitate to send us an email or use our feedback form.
If you uncover any errors, mistakes, or otherwise inaccurate information, please let us know.
The Book Of Engineering material is copyrighted, however it is provided with NO WARRANTY or LIABILITY. It's highly advisable to double-check important information with other sources. All applicable national and local legislation, standards and practices must be strictly followed and adhered to in this regard.